1MRK 511 557-UEN Rev. A
Section 17
17.1
Dimensions
Table 416: Dimensions of the IED - 3U full 19" rack
Description
Width
Height
Depth
Weight box
17.2
Power supply
Table 417: Power supply
Description
U
nominal
aux
U
variation
aux
Maximum load on auxiliary voltage
supply
Ripple in the DC auxiliary voltage
Maximum interruption time in the
auxiliary DC voltage without
resetting the IED
Resolution of the voltage
measurement in PSM module
17.3
Energizing inputs
17.4
Measuring inputs
Table 418: Measuring inputs
Description
Frequency
Rated frequency f
Operating range
Sampling frequency
Current inputs
Rated current I
Operating range
Table continues on next page
Technical Manual
Technical data
600PSM02
48, 60, 110, 125 V DC
80...120% of U
35 W for DC
Max 15% of the DC value (at frequency of 100 and 120 Hz)
50 ms at U
1 bit represents 1 V (+/- 1 VDC)
Value
50 or 60 Hz
r
f
r
4000 S/s at 50 Hz
4800 S/s at 60 Hz
1 or 5 A
r
0 – 500 A
© 2021 Hitachi Energy. All rights reserved.
Value
444 mm (17.48 inches)
132 mm (5.20 inches), 3U
249.5 mm (9.82 inches)
10 kg (<22.04 lbs)
(38.4...150 V DC)
n
aux
± 10%
1)
Technical data
D0E7937T201305151403 v2
D0E7960T201305151403 v2
600PSM03
110, 125, 220, 250 V DC
80...120% of U
(88...300 V DC)
n
1 bit represents 2 V (+/- 1 VDC)
GUID-80AA04F6-C989-4E8A-81C0-1A9A7458ADCC v7
D0E7961T201305151403 v4
Section 17
431