Section 11
Logic
•
Applicable to long time integration (≤999 999.9 seconds).
•
Supervision of limit transgression conditions and overflow.
•
Possibility defining a warning or alarm with resolution of 10 milliseconds.
•
Retain the integration value at a warning/alarm/overflow.
•
Possibilities for blocking and reset.
•
Report the integrated time
11.8.3
Function block
BLOCK
IN
RESET
IEC13000005 V1 EN-US
Figure 79:
11.8.4
Signals
Table 151: TEIGGIO Input signals
Name
BLOCK
IN
RESET
Table 152: TEIGGIO Output signals
Name
WARNING
ALARM
OVERFLOW
ACCTIME
11.8.5
Settings
Table 153: TEIGGIO Group settings (basic)
Name
Operation
tWarning
tAlarm
146
TEIGGIO
WARNING
ALARM
OVERFLOW
ACCTIME
IEC13000005-1-en.vsd
TEIGGIO function block
Type
BOOLEAN
BOOLEAN
BOOLEAN
Type
BOOLEAN
BOOLEAN
BOOLEAN
REAL
Values (Range)
Unit
0 - 1
-
1.00 - 999999.99
s
1.00 - 999999.99
s
© 2021 Hitachi Energy. All rights reserved.
Default
Description
0
Freeze the integration and block the other outputs
0
The input signal that is used to measure the elapsed time, when
its value is high
0
Reset the integration time
Description
Indicator of the integrated time has reached the warning limit
Indicator of the integrated time has reached the alarm limit
Indicator of the integrated time has reached the overflow limit
Integrated elapsed time in seconds
Step
Default
1
1
0.01
600.00
0.01
1200.00
1MRK 511 557-UEN Rev. A
GUID-6D50A060-7751-405B-AEC1-FAE942EBDA64 v1
GUID-18B28B75-45AA-4C69-A2A6-6475966BFB29 v1
PID-3403-INPUTSIGNALS v3
PID-3403-OUTPUTSIGNALS v3
GUID-7F971950-0DB6-4D9E-B4D7-CEF1E7AD078D v1
Description
Operation Off / On
Time limit for warning supervision
Time limit for alarm supervision
Technical Manual
PID-3403-SETTINGS v2