Settings; Operation Principle; Selection Of 3-Phase Signals 3Phselect; Identification - Hitachi Relion 650 Series Technical Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 557-UEN Rev. A
14.11.5

Settings

Table 377: 3PHSUM Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
SummationType
DFTReference
Table 378: 3PHSUM Non group settings (advanced)
Name
Values (Range)
FreqMeasMinVal
14.11.6

Operation principle

Summation block 3 phase 3PHSUM receives two groups of three-phase signals from Signal matrix
for analog inputs (SMAI) functions. The outputs are a linear combination of the corresponding input
signals, as per the SummationType setting.
The input signal REVROT is used to reverse the phase order of the output signal. DFTReference and
FreqMeasMinVal should be set the same as in the source SMAI functions.
Activating the BLOCK input will force all outputs of the function to 0.
14.12

Selection of 3-phase signals 3PHSELECT

14.12.1

Identification

Function description
Selection between two 3-phase
analog signals
14.12.2

Functionality

The purpose of the 3PHSELECT function is to connect the receiver functions to one out of two three-
phase analog signals. For example, in case of a tie-breaker application, where the connected load
can be supplied by either of the two sources available (refer
controlled by the IED in such a way that it can switch between the two sources (Source 1/Feeder 1
and Source 2/Feeder 2) seen by the breaker as required by the user. The 3PHSELECT function
allows selecting any of the available analog signals as reference signal or feedback signal without
the need for external logic.
Technical Manual
Unit
1 - 6
-
Group1+Group2
-
Group1-Group2
Group2-Group1
-(Group1+Group2)
InternalDFTRef
-
DFTRefGrp1
External DFT ref
Unit
5 - 200
%
IEC 61850 identification
3PHSELECT
© 2021 Hitachi Energy. All rights reserved.
Step
Default
1
1
-
Group1+Group2
-
InternalDFTRef
Step
Default
1
10
IEC 60617 identification
-
Figure
Basic IED functions
Description
Selection of one of the Global Base
Value groups
Summation type
DFT reference
Description
Amplitude limit for frequency calculation
in % of Ubase
GUID-33201BD4-5090-4D4A-9C83-2981EE4366A8 v1
GUID-E640AE9F-19A2-4C30-886A-26BD0C56A191 v1
ANSI/IEEE C37.2 device
number
-
GUID-6B318F9D-820F-4E13-A7AC-985501A07D50 v2
177), the tie-breaker should be
Section 14
PID-1250-SETTINGS v13
SEMOD55749-4 v4.1.2
399