Basic IED functions
Name
DIAGSMPLT
DIAGSYNMU
DIAGTSTMD
14.19.5

Settings

Table 395: SRCSELECT Non group settings (advanced)
Name
InputSelect
14.19.6

Operation principle

The source selector function is a multiplexer, where the output is selected from one of the eight input
phase group with a setting. It selects one of the analog input groups and forwards the selected input
group to the pre-processing component connected to its output. A group of transformer module
channels or merging unit channels can be connected to the source selector as the input source.
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
IEC12000103 V1 EN-US
Figure 185: Source selector application
Figure 185
"INPUT1", the INPUT1 channel link strings are passed to the pre-processing component, and so
forth. Based on that link, the pre-procesing component fetches the data from the particular channel.
The IED supports four IEC 61850-9-2(LE) merging unit streams, wherein each stream has four sets
of current and voltage signals. In a hybrid configuration, the current and voltage can be either from a
conventional CT/VT (connection through TRM) or through the IEC 61850-9-2(LE) MU. The eight
input groups are provided per instance for the selection, out of which the last four input groups can
be connected to the merging unit signals, as there are diagnostic status signals that need to be
selected and provided as an output from the function.
414
Type
BOOLEAN
BOOLEAN
BOOLEAN
Values (Range)
Unit
INPUT1
-
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
INPUT7
INPUT8
SRCSELECT
InputSelect
depicts the source selector embedded in an application. When InputSelect is set to
© 2021 Hitachi Energy. All rights reserved.
Description
Sample lost; Current sample estimated for selected MU
smpSynch flag in frame for selected MU not ok
Used channel from selected MU is in testmode
Step
Default
-
INPUT1
SMAI
1MRK 511 557-UEN Rev. A
Description
Input group selection to output
GUID-50D0531A-AF51-4762-A957-21957195F2DF v2