1MRK 511 557-UEN Rev. A
Description
Radiated, amplitude-
modulated
Fast transient disturbance tests
Communication ports
Other ports
Surge immunity test
Communication ports
Other ports
Power supply
Power frequency (50 Hz) magnetic
field
3 s
Continuous
Pulse magnetic field immunity test
Damped oscillatory magnetic field
Power frequency immunity test
Common mode
Differential mode
Voltage dips and short
interruptionsc on DC power supply
Voltage dips and interruptions on
AC power supply
Electromagnetic emission tests
Conducted, RF-emission
(mains terminal)
0.15...0.50 MHz
Table continues on next page
Technical Manual
Type test value
20 V/m (rms), f=80...1000 MHz and
f=1.4...2.7 GHz
4 kV
4 kV
1 kV line-to-earth
2 kV line-to-earth, 1 kV line-to-line
4 kV line-to-earth, 2 kV line-to-line
1000 A/m
100 A/m
1000 A/m
100 A/m, 100 kHz and 1 MHz
300 V rms
150 V rms
Dips:
40%/200 ms
70%/500 ms
Interruptions:
0...50 ms: No restart
0...∞ s : Correct behaviour at power
down
Dips:
40% 10/12 cycles at 50/60 Hz
70% 25/30 cycles at 50/60 Hz
Interruptions:
0...50 ms: No restart
0...∞ s: Correct behaviour at power
down
<79 dB(µV) quasi peak
<66 dB(µV) average
© 2021 Hitachi Energy. All rights reserved.
Technical data
Reference
IEC 61000-4-3, level 3
IEC 60255-22-3
ANSI C37.90.2-2004
IEC 61000-4-4
IEC 60255-22-4, class A
ANSI C37.90.1-2012
IEC 61000-4-5
IEC 60255-22-5
IEC 61000-4-8, level 5
IEC 61000-4-9, level 5
IEC 61000-4-10, level 5
IEC 60255-22-7, class A
IEC 61000-4-16
IEC 60255-11
IEC 61000-4-11
IEC 60255-11
IEC 61000-4-11
EN 55011, class A
IEC 60255-25
ANSI C63.4, FCC
Section 17