Setting Parameters For Precision Binary Inputs - Hitachi Relion 650 Series Technical Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 557-UEN Rev. A
Name
Values (Range)
Threshold8
DebounceTime8
OscillationCount8
OscillationTime8
Threshold9
DebounceTime9
OscillationCount9
OscillationTime9
4.1.3.2

Setting parameters for precision binary inputs

Table 7:
PIO_12PBI Non group settings (basic)
Name
Values (Range)
BatteryVoltage
Table 8:
PIO_12PBI Non group settings (advanced)
Name
Values (Range)
Threshold1
DebounceTimeOn1
DebounceTimeOff1
OscillationCntOn1
OscillationCntOff1
OscillationTimeOn1
OscillationTimeOff1
Threshold2
DebounceTimeOn2
DebounceTimeOff2
OscillationCntOn2
OscillationCntOff 2
OscillationTimeOn2
OscillationTimeOff2
Threshold3
DebounceTimeOn3
DebounceTimeOff3
OscillationCntOn3
Table continues on next page
Technical Manual
Unit
6 - 900
%UB
0.000 - 0.100
s
0 - 255
-
0.000 - 600.000
s
6 - 900
%UB
0.000 - 0.100
s
0 - 255
-
0.000 - 600.000
s
For Switchsync PWC600, Battery voltage is usually entered in SST, under the
Power System milestone, and distributed to all hardware modules.
Unit
24 - 250
-
Unit
15 - 221
-
0.0000 - 0.1270
-
0.0000 - 0.1270
-
0 - 255
-
0 - 255
-
0.000 - 600.000
-
0.000 - 600.000
-
15 - 221
-
0.0000 - 0.1270
-
0.0000 - 0.1270
-
0 - 255
-
0 - 255
-
0.000 - 600.000
-
0.000 - 600.000
-
15 - 221
-
0.0000 - 0.1270
-
0.0000 - 0.1270
-
0 - 255
-
© 2021 Hitachi Energy. All rights reserved.
Step
Default
1
65
0.001
0.005
1
0
0.001
0.000
1
65
0.001
0.005
1
0
0.001
0.000
Step
Default
1
110
Step
Default
1
65
0.0001
0.0050
0.0001
0.0050
1
0
1
0
0.001
0.000
0.001
0.000
1
65
0.0001
0.0050
0.0001
0.0050
1
0
1
0
0.001
0.000
0.001
0.000
1
65
0.0001
0.0050
0.0001
0.0050
1
0
Binary inputs and outputs
Description
Threshold in percentage of station
battery voltage for input 8
Debounce time for input 8
Oscillation count for input 8
Oscillation time for input 8
Threshold in percentage of station
battery voltage for input 9
Debounce time for input 9
Oscillation count for input 9
Oscillation time for input 9
GUID-4D21A653-A108-4D4A-9B15-24CEEC483C34 v2
Description
Station battery voltage
Description
Threshold in percentage of station
battery voltage for input 1
Debounce time On for input 1
Debounce time Off for input 1
OscillationCountOn for input 1
OscillationCountOff for input 1
OscillationTimeOn for input 1
OscillationTimeOff for input 1
Threshold in percentage of station
battery voltage for input 2
Debounce time On for input 2
Debounce time Off for input 2
OscillationCountOn for input 2
OscillationCountOff for input 2
OscillationTimeOn for input 2
OscillationTimeOff for input 2
Threshold in percentage of station
battery voltage for input 3
Debounce time On for input 3
Debounce time Off for input 3
OscillationCountOn for input 3
Section 4
PID-3915-SETTINGS v1
35

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Switchsync pwc600

Table of Contents