Hitachi Relion 650 Series Technical Manual page 340

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 12
Monitoring
Name
CLTIMPRIL1
CLTIMPRIL2
CLTIMPRIL3
LONOTIML1
LONOTIML2
LONOTIML3
LONCTIML1
LONCTIML2
LONCTIML3
LOPRITIML1
LOPRITIML2
LOPRITIML3
WIERCD
CMDERCD
OPSHTDONE
CLSHTDONE
COORBLSS
WIERL1
WIERL2
WIERL3
CMDER
LERACTIVE
LOPSUC
LOPFAIL
LCLSUC
LCLFAIL
TIMOUTAL
LONOL1AL
LONOL2AL
LONOL3AL
LONCL1AL
LONCL2AL
LONCL3AL
Table continues on next page
334
Type
Description
REAL
Final average value of primary contact operating time for close
operations for phaseL1
REAL
Final average value of primary contact operating time for close
operations for phaseL2
REAL
Final average value of primary contact operating time for close
operations for phaseL3
REAL
NO contact operating time for last operation for phaseL1
REAL
NO contact operating time for last operation for phaseL2
REAL
NO contact operating time for last operation for phaseL3
REAL
NC contact operating time for last operation for phaseL1
REAL
NC contact operating time for last operation for phaseL2
REAL
NC contact operating time for last operation for phaseL3
REAL
Primary contact operating time for last operation for phaseL1
REAL
Primary contact operating time for last operation for phaseL2
REAL
Primary contact operating time for last operation for phaseL3
INTEGER
Integer for indicating type of wiring error
INTEGER
Integer for indicating type of command error
INTEGER
Number of successful open shots performed
INTEGER
Number of successful close shots performed
INTEGER
Co-ordination output to SSCPOW to indicate the command
BOOLEAN
Indication for wiring error in phaseL1
BOOLEAN
Indication for wiring error in phaseL2
BOOLEAN
Indication for wiring error in phaseL3
BOOLEAN
Indication for command error
BOOLEAN
Indication for CB test mode is active
BOOLEAN
Indication for successful last open operation
BOOLEAN
Indication for unsuccessful last open operation
BOOLEAN
Indication for successful last close operation
BOOLEAN
Indication for unsuccessful last close operation
BOOLEAN
Signal time out for not receiving auxiliary contact or primary
contact feedback
BOOLEAN
Alarm if NO contact operating time last operation for phaseL1 is
not in the tolerance limit
BOOLEAN
Alarm if NO contact operating time last operation for phaseL2 is
not in the tolerance limit
BOOLEAN
Alarm if NO contact operating time last operation for phaseL3 is
not in the tolerance limit
BOOLEAN
Alarm if NC contact operating time last operation for phaseL1 is
not in the tolerance limit
BOOLEAN
Alarm if NC contact operating time last operation for phaseL2 is
not in the tolerance limit
BOOLEAN
Alarm if NC contact operating time last operation for phaseL3 is
not in the tolerance limit
© 2021 Hitachi Energy. All rights reserved.
1MRK 511 557-UEN Rev. A
Technical Manual