Section 5
Local HMI
Activating
signal
LED
Reset
D0E10932T201305151403 V1 EN-US
Figure 17:
That means if an indication with higher priority has reset while an indication with lower priority still is
active at the time of reset, the LED will change color according to
Activating
signal GREEN
Activating
signal RED
LED
Reset
D0E13171T201305151403 V1 EN-US
Figure 18:
Sequence 6 LatchedReset-S
In this mode all activated LEDs, which are set to Sequence 6 (LatchedReset-S), are automatically
reset at a new disturbance when activating any input signal for other LEDs set to Sequence 6
LatchedReset-S. Also in this case indications that are still activated will not be affected by manual
reset, that is, immediately after the positive edge of that the manual reset has been executed a new
reading and storing of active signals is performed. LEDs set for sequence 6 are completely
independent in its operation of LEDs set for other sequences.
Timing diagram for sequence 6
Figure 19
50
Operating Sequence 5 LatchedColl-S
R
Operating sequence 5, two colors
shows the timing diagram for two indications within one disturbance.
© 2021 Hitachi Energy. All rights reserved.
IEC01000235_2_en.vsd
Figure
18.
G
IEC09000316_1_en.vsd
1MRK 511 557-UEN Rev. A
D0E5669T201305151403 v1
D0E5430T201305151403 v1
D0E5431T201305151403 v1