Hitachi Relion 650 Series Technical Manual page 419

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 557-UEN Rev. A
Name
INPUT6-N
DIAG6DATA
DIAG6SYNCH
DIAG6SMPLT
DIAG6SYNMU
DIAG6TSTMD
INPUT7-1
INPUT7-2
INPUT7-3
INPUT7-N
DIAG7DATA
DIAG7SYNCH
DIAG7SMPLT
DIAG7SYNMU
DIAG7TSTMD
INPUT8-1
INPUT8-2
INPUT8-3
INPUT8-N
DIAG8DATA
DIAG8SYNCH
DIAG8SMPLT
DIAG8SYNMU
DIAG8TSTMD
Table 394: SRCSELECT Output signals
Name
OUTPUT-1
OUTPUT-2
OUTPUT-3
OUTPUT-N
DIAGDATA
DIAGSYNCH
Table continues on next page
Technical Manual
Type
Default
Description
STRING
0
Fourth analog input used for residual or neutral quantity of
INPUT6
BOOLEAN
0
Serious data loss from MU over INPUT6 group
BOOLEAN
0
MU clock not synced to same clock as IED over INPUT6 group
BOOLEAN
0
Sample lost; Current sample estimated for MU over INPUT6
group
BOOLEAN
0
smpSynch flag in frame for MU not ok over INPUT6 group
BOOLEAN
0
Used channel from MU is in testmode over INPUT6 group
STRING
0
First analog input used for phase L1 or L1-L2(not in case of MU)
quantity of INPUT7
STRING
0
Second analog input used for phase L2 or L2-L3(not in case of
MU) quantity of INPUT7
STRING
0
Third analog input used for phase L3 or L3-L1(not in case of MU)
quantity of INPUT7
STRING
0
Fourth analog input used for residual or neutral quantity of
INPUT7
BOOLEAN
0
Serious data loss from MU over INPUT7 group.
BOOLEAN
0
MU clock not synced to same clock as IED over INPUT7 group
BOOLEAN
0
Sample lost; Current sample estimated for MU over INPUT7
group
BOOLEAN
0
smpSynch flag in frame for MU not ok over INPUT7 group
BOOLEAN
0
Used channel from MU is in testmode over INPUT7 group
STRING
0
First analog input used for phase L1 or L1-L2(not in case of MU)
quantity of INPUT8
STRING
0
Second analog input used for phase L2 or L2-L3(not in case of
MU) quantity of INPUT8
STRING
0
Third analog input used for phase L3 or L3-L1(not in case of MU)
quantity of INPUT8
STRING
0
Fourth analog input used for residual or neutral quantity of
INPUT8
BOOLEAN
0
Serious data loss from MU over INPUT8 group.
BOOLEAN
0
MU clock not synced to same clock as IED over INPUT8 group
BOOLEAN
0
Sample lost; Current sample estimated for MU over INPUT8
group
BOOLEAN
0
smpSynch flag in frame for MU not ok over INPUT8 group
BOOLEAN
0
Used channel from MU is in testmode over INPUT8 group
Type
Description
STRING
Selected Output -1
STRING
Selected Output -2
STRING
Selected Output -3
STRING
Selected Output -N
BOOLEAN
Serious data loss from selected MU
BOOLEAN
Selected MU clock not synced to same clock as IED
© 2021 Hitachi Energy. All rights reserved.
Section 14
Basic IED functions
PID-3894-OUTPUTSIGNALS v1
413

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Switchsync pwc600

Table of Contents