Hitachi Relion 650 Series Technical Manual page 240

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 12
Monitoring
Trigger
IEC12000047 V1 EN-US
Figure 111: Trigger connections for operation log instances
Configure the instances in ACT such that
Individual instances do not have any input or output daisy chain connection to any other
operation log component.
Primary instances have only output daisy chain connection to the secondary operation log
component.
Secondary instances have input daisy chain connection to a primary or secondary operation log
component and possibly an output daisy chain connection to another secondary instance.
To prevent wrong reporting after configuration changes, the following procedure should be observed:
1.
Download the operation log database through WHMI.
2.
Write configuration changes to the IED.
3.
Clear all operation records and fingerprint records in the IED.
234
Primary 1
OPERLOG
Instance 1
Primary 2
OPERLOG
Instance 4
Individual 1
OPERLOG
Instance 7
With one or more operation records already stored in the database, changes in
OPERLOG related ACT configuration or in OPERLOG parameters may lead to
wrong reporting on LHMI or WHMI.
© 2021 Hitachi Energy. All rights reserved.
Secondary 1
Secondary 2
OPERLOG
OPERLOG
Instance 2
Instance 3
Secondary 3
Secondary 4
OPERLOG
OPERLOG
Instance 5
Instance 6
Individual 2
Individual 3
OPERLOG
OPERLOG
Instance 8
Instance 9
IEC12000047-1-EN.vsd
1MRK 511 557-UEN Rev. A