Fixed Signals Fxdsign; Identification; Functionality - Hitachi Relion 650 Series Technical Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 557-UEN Rev. A
Function block
SI_IN*
IEC09000307 V1 EN-US
Figure 72:
Signals
Table 134: INDEXTSPQT Input signals
Name
SI_IN
Table 135: INDEXTSPQT Output signals
Name
SI_OUT
TIME
BLOCKED
SUBST
INVALID
TEST
Settings
The function does not have any parameters available in Local HMI or Protection and Control IED
Manager (PCM600).
11.2

Fixed signals FXDSIGN

11.2.1

Identification

Function description
Fixed signals
11.2.2

Functionality

The Fixed signals function FXDSIGN generates nine pre-set (fixed) signals that can be used in the
configuration of an IED, either for forcing the unused inputs in other function blocks to a certain level/
value, or for creating certain logic. Boolean, integer, floating point, string, and group types of signals
are available.
Technical Manual
INDEXTSPQT
SI_OUT
TIME
BLOCKED
SUBST
INVALID
TEST
IEC09000307-1-en.vsd
INDEXTSPQT function block
Type
Default
BOOLEAN
0
Type
BOOLEAN
GROUP SIGNAL
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
© 2021 Hitachi Energy. All rights reserved.
Description
Single indication
Description
Single indication
Timestamp of input
Blocked for update
Substituted
Invalid value
Testmode
IEC 61850
IEC 60617
identification
identification
FXDSIGN
-
Section 11
GUID-0525A2AE-A669-4095-BE5C-89E36C9962E7 v2
PID-1602-INPUTSIGNALS v13
PID-1602-OUTPUTSIGNALS v13
GUID-50A2CEA0-2781-4C5F-B184-F09FC666876F v1
D0E7202T201305151403 v1
ANSI/IEEE C37.2
device number
-
D0E7196T201305151403 v2
Logic
135