Monitored Data; Denial Of Service, Frame Rate Control For Lan1 Port Doslan1; Identification; Function Block - Hitachi Relion 650 Series Technical Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 557-UEN Rev. A
14.18.2.5

Monitored data

Table 390: DOSFRNT Monitored data
Name
State
Quota
IPPackRecNorm
IPPackRecPoll
IPPackDisc
NonIPPackRecNorm
NonIPPackRecPoll
NonIPPackDisc
14.18.3

Denial of service, frame rate control for LAN1 port DOSLAN1

14.18.3.1

Identification

Function description
Denial of service, frame rate control for
LAN1 port
14.18.3.2

Function block

D0E13231T201305151403 V1 EN-US
Figure 183: DOSLAN1 function block
14.18.3.3

Signals

Table 391: DOSLAN1 Output signals
Name
LINKUP
WARNING
ALARM
Technical Manual
Type
INTEGER
INTEGER
INTEGER
INTEGER
INTEGER
INTEGER
INTEGER
INTEGER
DOSLAN1
LINKUP
WARNING
ALARM
IEC09000134-1-en.vsd
Type
BOOLEAN
BOOLEAN
BOOLEAN
© 2021 Hitachi Energy. All rights reserved.
Values (Range)
Unit
0=Off
-
1=Normal
2=Throttle
3=DiscardLow
4=DiscardAll
5=StopPoll
-
%
-
-
-
-
-
-
-
-
-
-
-
-
IEC 61850
IEC 60617
identification
identification
DOSLAN1
Description
Ethernet link status
Frame rate is higher than normal state
Frame rate is higher than throttle state
Description
Frame rate control state
Quota level in percent 0-100
Number of IP packets received in normal
mode
Number of IP packets received in polled
mode
Number of IP packets discarded
Number of non IP packets received in
normal mode
Number of non IP packets received in
polled mode
Number of non IP packets discarded
ANSI/IEEE C37.2
device number
-
-
Section 14
Basic IED functions
D0E7268T201305151403 v1
D0E7337T201305151403 v1
D0E7343T201305151403 v1
D0E7271T201305151403 v1
409