Section 9
Control
Name
STCLANGL3
STOPANGL1
STOPANGL2
STOPANGL3
OPREF
CNTRLDEL
9.3.5

Settings

Table 34:
SSCPOW Non group settings (basic)
Name
Operation
CompSigLosAlm
ContDelayExdAlm
RefSignalLossAlm
UncontSwitchAlm
Table 35:
SSCPOW Group settings (basic)
Name
CntrldOperType
CloseTargetL1
CloseTargetL2-L1
CloseTargetL3-L1
InputSelect
OpenTargetL1
OpenTargetL2-L1
OpenTargetL3-L1
OpenRef
76
Type
REAL
REAL
REAL
REAL
BOOLEAN
REAL
Values (Range)
Unit
Off
-
On
Disable
-
Enable
Disable
-
Enable
Disable
-
Enable
Disable
-
Enable
Values (Range)
Unit
Close
-
Open
Open & Close
-1800 - 1800
Deg
-1800 - 1800
Deg
-1800 - 1800
Deg
Load 1
-
Load 2
-1800 - 1800
Deg
-1800 - 1800
Deg
-1800 - 1800
Deg
Voltage
-
Current
© 2021 Hitachi Energy. All rights reserved.
Description
Target current making angle for phase L3, in deg
Target current interruption angle for phase L1, in deg
Target current interruption angle for phase L2, in deg
Target current interruption angle for phase L3, in deg
Reference signal used in last controlled opening operation
Controller delay from command input to last command output in
last switching operation, in ms
Step
Default
-
On
-
Disable
-
Disable
-
Disable
-
Disable
Step
Default
-
Close
1
0
1
0
1
0
-
Load 1
1
0
1
0
1
0
-
Voltage
1MRK 511 557-UEN Rev. A
Description
Operation Mode Off / On
Enable / Disable alarm for loss of
compensation signal
Enable / Disable alarm for maximum
controller delay exceeded
Enable / Disable alarm for reference
signal lost
Enable / disable alarm for uncontrolled
switching operation executed
Description
Switching operation(s) to be controlled
Target making angle (relative to positive
zero crossing) for L1 phase
Target making angle (relative to
CloseTargetL1) for L2 phase
Target making angle (relative to
CloseTargetL1) for L3 phase
Source of external target making angles
to be used for controlled closing
Target contact separation angle (relative
to positive zero crossing) for L1 phase
Target contact separation angle (relative
to OpenTargetL1) for L2 phase
Target contact separation angle (relative
to OpenTargetL1) for L3 phase
Reference signal for controlled opening
operations
Technical Manual
PID-7616-SETTINGS v2