12.12.5

Settings

Table 226: MVGGIO Non group settings (basic)
Name
Values (Range)
BasePrefix
MV db
MV zeroDb
MV hhLim
MV hLim
MV lLim
MV llLim
MV min
MV max
MV dbType
MV limHys
12.12.6

Monitored data

Table 227: MVGGIO Monitored data
Name
VALUE
RANGE
12.12.7

Operation principle

Upon receiving an analog signal at its input, IEC61850 generic communication I/O functions
(MVGGIO) will give the instantaneous value of the signal and the range, as output values. At the
same time, it will send over IEC 61850-8-1 the value, to other IEC 61850 clients in the substation.
The principles of zero-point clamping, range supervision, and value reporting are explained in
Section
settings.
Technical Manual
Unit
micro
-
milli
unit
kilo
Mega
Giga
Tera
1 - 300
Type
0 - 100000
m%
-5000.00 - 5000.00
xBase
-5000.00 - 5000.00
xBase
-5000.00 - 5000.00
xBase
-5000.00 - 5000.00
xBase
-5000.00 - 5000.00
xBase
-5000.00 - 5000.00
xBase
Cyclic
-
Dead band
Int deadband
0.000 - 100.000
%
Type
REAL
INTEGER
12.1.8.1. For MVGGIO, the measurement range is defined by the MV min and MV max
© 2021 Hitachi Energy. All rights reserved.
Step
Default
-
unit
1
10
1
500
0.01
900.00
0.01
800.00
0.01
-800.00
0.01
-900.00
0.01
-1000.00
0.01
1000.00
-
Dead band
0.001
5.000
Values (Range)
Unit
-
-
0=Normal
-
1=High
2=Low
3=High-High
4=Low-Low
D0E8316T201305151403 v1
Description
Base prefix (multiplication factor)
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Zero point clamping in 0,001% of range
High High limit multiplied with the base
prefix (multiplication factor)
High limit multiplied with the base prefix
(multiplication factor)
Low limit multiplied with the base prefix
(multiplication factor)
Low Low limit multiplied with the base
prefix (multiplication factor)
Minimum value multiplied with the base
prefix (multiplication factor)
Maximum value multiplied with the base
prefix (multiplication factor)
Reporting type
Hysteresis value in % of range (common
for all limits)
D0E8314T201305151403 v1
Description
Magnitude of deadband value
Range
D0E8254T201305151403 v2
Section 12
Monitoring
221

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Switchsync pwc600

Table of Contents