Operation Principle; Goose Function Block To Receive An Integer Value Gooseintrcv; Identification; Functionality - Hitachi Relion 650 Series Technical Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 13
Station communication
13.3.6

Operation principle

DPOUT represents the double-point status (transmitted via IEC 61850 GOOSE message) of a
switching element according to the following table.
DPOUT (integer value)
The DATAVALID output will be 1 (high) as long as the incoming message contains valid data. In case
of invalid data DPOUT will be forced to 0.
The COMMVALID output will become 0 (low) when the subscribed GOOSE messages are not
received as expected. In this case DPOUT will retain the last valid value.
The TEST output will be 1 (high) when the sending IED is in test mode.
13.4
GOOSE function block to receive an integer value
GOOSEINTRCV
13.4.1

Identification

Function description
GOOSE function block to receive an
integer value
13.4.2

Functionality

GOOSEINTRCV is used to receive an integer value using IEC 61850 protocol via GOOSE.
13.4.3

Function block

BLOCK
D0E13792T201305151403 V1 EN-US
Figure 155: GOOSEINTRCV function block
350
0
1
2
3
The input of this GOOSE block must be linked in SMT to receive the double point
values.
The implementation for IEC 61850 quality data handling is restricted to a simple
level. If quality data validity is GOOD then the DATAVALID output will be HIGH. If
quality data validity is INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the DATAVALID output will be LOW.
GOOSEINTRCV
^INTOUT
DATAVALID
COMMVALID
TEST
IEC10000250-1-en.vsd
© 2021 Hitachi Energy. All rights reserved.
DPOUT (binary value)
00
01
10
11
IEC 61850
IEC 60617
identification
identification
GOOSEINTRCV
-
1MRK 511 557-UEN Rev. A
D0E7462T201305151403 v1
Status
intermediate / unknown
off / open
on / closed
faulty
D0E7444T201305151403 v1
ANSI/IEEE C37.2
device number
-
D0E7459T201305151403 v1
D0E7450T201305151403 v1