Disturbance Report Drprdre; Identification; Function Block; Signals - Hitachi Relion 650 Series Technical Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 12
Monitoring
12.4.2

Disturbance report DRPRDRE

12.4.2.1

Identification

Function description
Disturbance report
12.4.2.2

Function block

D0E13244T201305151403 V1 EN-US
Figure 97:
12.4.2.3

Signals

Table 203: DRPRDRE Output signals
Name
DRPOFF
RECSTART
RECMADE
CLEARED
MEMUSED
12.4.2.4

Settings

Table 204: DRPRDRE Non group settings (basic)
Name
Operation
PreFaultRecT
PostFaultRecT
TimeLimit
PostRetrig
MaxNoStoreRec
ZeroAngleRef
OpModeTest
184
DRPRDRE
DRPOFF
RECSTART
RECMADE
CLEARED
MEMUSED
IEC09000346-1-en.vsd
DRPRDRE function block
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Values (Range)
Unit
Off
-
On
0.05 - 3.00
s
0.1 - 10.0
s
0.5 - 8.0
s
Off
-
On
10 - 200
-
1 - 30
Ch
Off
-
On
© 2021 Hitachi Energy. All rights reserved.
IEC 61850
IEC 60617
identification
identification
DRPRDRE
-
Description
Disturbance report function turned off
Disturbance recording started
Disturbance recording made
All disturbances in the disturbance report cleared
More than 80% of memory used
Step
Default
-
Off
0.01
0.10
0.1
0.5
0.1
1.0
-
Off
1
200
1
1
-
Off
1MRK 511 557-UEN Rev. A
D0E7504T201305151403 v1
D0E7581T201305151403 v1
ANSI/IEEE C37.2
device number
-
D0E7476T201305151403 v1
D0E7764T201305151403 v1
Description
Operation Off/On
Pre-fault recording time
Post-fault recording time
Fault recording time limit
Post-fault retrig enabled (On) or not (Off)
Maximum number of stored disturbances
Trip value recorder, phasor reference
channel
Operation mode during test mode