1MRK 511 557-UEN Rev. A
AARCTMLX = Electrical Interruption time – INPRIOPLX
Refer
Section
ACBMSCBR also evaluates error target value ERELOTOLX (in milliseconds) for open operations as
difference between AELORTOLX and PELORTOLX,
ERELOTOLX = AELORTOLX – PELORTOLX
The same value is also given at the output ERELORTLX for opening operations.
Re-strike/re-ignition detection and count
In every controlled opening operation, ACBMSCBR checks the primary current signal selected by
FeedbackSigO for re-ignition/re-strike (see
activating the RSTRDETLX output. Specifically, a re-ignition or re-strike is declared when final
current interruption is detected later than 1/8 power cycle after the predicted interruption instant,
AELORTOLX – PELORTOLX > T/8.
Every re-ignition/re-strike increments an internal counter. The counter value is published at the
RTKCTLX output. It can be reset to zero by activating the RESRCNT input.
12.18.7.12

Mechanical monitoring

Based on the detection of auxiliary contact changeover, ACBMSCBR provides the following
mechanical monitoring values at its outputs.
Mechanical operating time
Initial mechanical delay
Mechanical movement time
Mechanical operating time
ACBMSCBR provides two values during any open/close operation, namely the predicted and the
actual (estimated) mechanical operating time. The predicted value is published as soon as a Close or
Trip command is received on the CLCMDINP or OPCMDINP input and the actual value is published
300 ms after receiving the CCLCMDLX or COPCMDLX command.
The predicted mechanical opening time PMCORTOLX (in milliseconds) is defined as:
PMCORTOLX = INPRIOPLX+ OPENCOMP
where OPENCOMP is the total compensation value for the mechanical opening time.
The same value is also given at the output PMCORTLX for opening operations..
The predicted mechanical closing time PMCORTCLX (in milliseconds) is defined as:
PMCORTCLX = INPRICLLX + CLOSECOMP + ADAPTCLLX
where CLOSECOMP is the total compensation value for the mechanical closing time.
The same value is also given at the output PMCORTLX for closing operations.
The actual mechanical opening time AMCOTOLX (in milliseconds) is defined as:
AMCOTOLX = Mechanical opening time
Refer
Section
The same value is also given at the output AMCOTMLX for opening operations.
Technical Manual
12.18.7.10.2.
12.18.7.10.5.
© 2021 Hitachi Energy. All rights reserved.
Section
12.18.7.10.3) and indicates this event by
Section 12
Monitoring
GUID-6ECFB1F1-89EF-4F57-BE3C-C187CADCA6AA v2
GUID-98FEE49A-E289-4449-9F44-246854E5A6A9 v2
GUID-85FA1F76-5298-4255-BA24-744AA5037638 v2
GUID-CC278928-DF94-41A7-AE94-948E15C61CA7 v2
GUID-F2B9F2A6-198D-497E-BE79-59D63CEAA52C v2
303

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Switchsync pwc600

Table of Contents