Maintenance 8. Trouble Shooting
Hardware
No.
Emergency stop circuit failure was detected.
9001
Disconnection or other failure was found in
one of the redundant inputs.
Safeguard circuit failure was detected.
9002
Disconnection or other failure was found in
one of the redundant inputs.
Battery voltage of the CPU board backup is
9011
lower than the specified voltage. Replace the
CPU board battery.
5V input voltage for CPU board is lower
9012
than the specified voltage.
24 V input voltage for the motor brake,
9013
encoder and fan is lower than the specified
voltage.
Internal temperature of the Controller is
9014
higher than the specified temperature.
Rotating speed of the controller fan is below
9015
the allowed speed. (FAN1)
Rotating speed of the controller fan is below
9016
the allowed speed. (FAN2)
Internal temperature of the Controller is
9017
higher than the specified temperature.
Initialization failure.
9100
Failed to allocate memory.
9101
Message queue has become full.
The Fieldbus I/O driver is in an abnormal
9233
state.
9234
Fieldbus I/O driver initialization failure.
RAS circuit detected a servo system
9610
malfunction. Reboot the controller. Check
for noise. Replace the controller.
Servo CPU internal RAM failure. Reboot the
9611
controller. Check for noise. Replace the
DMB.
RAM for the main and servo CPU
communication
9612
controller. Check for noise. Replace the
DMB.
Servo CPU internal RAM failure. Reboot the
9613
controller. Check for noise. Replace the
DMB.
Initialization communication of main CPU
and
servo CPU failure.
9614
Controller.
Check for noise.
DMB.
238
Message
failure.
Reboot
the
Reboot the
Replace
Remedy
Check whether no disconnection, earth fault, or
short-circuit of the emergency stop input signal
exits. Then reboot the controller.
Check whether no disconnection, earth fault, or
short-circuit of the safeguard input signal exits.
Then reboot the controller.
Replace the battery for the CPU board
immediately. Keep the controller ON as long
as possible until the battery is replaced.
If normal voltage is not generated by 5V power
supply alone, replace the power supply.
If normal voltage is not generated by 24V
power supply alone, replace the power supply.
Stop the controller as soon as possible and
check whether the ambient temperature of the
controller is not high.
Check whether the filter is not clogged up.
Check whether the filter is not clogged up. If
the warning is not cleared after the controller is
rebooted, replace the fan.
Check whether the filter is not clogged up. If
the warning is not cleared after the controller is
rebooted, replace the fan.
Stop the controller as soon as possible and
check whether the ambient temperature of the
controller is not high.
Check whether the filter is not clogged up.
Reboot the controller.
The module is broken or the controller
software is damaged. Restore the controller
firmware.
The module is broken or the controller
software is damaged. Restore the controller
firmware.
Check the noise countermeasures.
Replace the DMB.
Check the noise countermeasures.
Replace the DMB.
Check the noise countermeasures.
Replace the DMB.
Check the noise countermeasures.
Replace the DMB.
Check the noise countermeasures.
Replace the DMB.
Note 1
Note 2
Current
Boundary
value
value
Current
Boundary
value
value
Current
Boundary
value
value