Installing A Remote T/H Sensor For The Smart Cooling Product - Huawei FusionModule500 User Manual

Smart mini data center
Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual
Ensure that the PAD is installed securely and reliably.
Figure 4-51 Installing a PAD
Step 5 Connect the cable from the USB port on the ECC800-Pro to the charging port on
the PAD.
If the PAD screen needs to remain on for a long time during usage, adjust the
brightness to below 80%.
----End

4.2.6.3 Installing a Remote T/H Sensor for the Smart Cooling Product

Procedure
Step 1 Install a T/H sensor.
1.
2.
Step 2 Set the DIP switch address of the T/H sensor on the front door to 2 and that of
the T/H sensor on the rear door to 1.
Issue 02 (2020-12-25)
NO TICE
NO TICE
Open the front and rear doors of the cabinet.
Unpack the two T/H sensors, and attach one to the 33 U position on the right
post of the front door and the other to the 3–4 U position on the right post of
the rear door of the cabinet.
NO TE
The installation positions of the T/H sensors can be adjusted as required.