Figure 6-29 Connecting a new water detection cable
(1) Conversion cable end B, connected to the
water detection cable
Step 3 Connect the network cable between the water detector and ECC800-Pro, immerse
the water detection cable in water, and check whether an alarm is generated. If an
alarm is generated, the component is functional.
----End

6.4.3.12 Replacing an Electrode Water Sensor

Prerequisites
Procedure
Step 1 Disconnect the cable between the water sensor and the ECC800-Pro.
Step 2 Remove the faulty water sensor.
Step 3 Place the new water sensor in the correct position.
Step 4 Connect the water sensor cable connected to the ECC800-Pro to the new water
sensor.
----End
Issue 02 (2020-12-25)
NO TE
The water detection cable and conversion cable are interconnected through the male and
female connectors.
Recommended tools and materials: Phillips screwdriver, crimping tool
A water sensor needs to be replaced.
A spare water sensor is available.
Copyright © Huawei Technologies Co., Ltd.