Huawei FusionModule500 User Manual page 245

Smart mini data center
Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual
Maintenance
Area
UPS
Lithium battery
Issue 02 (2020-12-25)
Maintenance
Item
Operating
environment
Liquid crystal
display (LCD)
Battery
management
alarm
Copyright © Huawei Technologies Co., Ltd.
Operation
-
-
-
Expected Result
Troubleshootin
g
● Ambient
● If the
temperature:
0–40°C
● Humidity:
0%–95% RH
(non-
condensing)
● If the input
According to the
If an alarm is
status icons on
present, rectify
the LCD, all units
the fault by
are operating
checking the
properly. No
device status
fault or alarm
and parameters.
information is
found in the
active and
historical alarm
records.
No battery
Identify the
management
cause of an
alarm is
alarm based on
generated.
the alarm
information.
6 O&M
temperature
or humidity
is abnormal,
check the
smart
cooling
product
status.
voltage is
abnormal,
check the
power grid
status and
input cable
connection.
235

Advertisement

Table of Contents
loading

This manual is also suitable for:

V100r021c00

Table of Contents