Technical Specifications - Huawei FusionModule500 User Manual

Smart mini data center
Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual
Item
Indoor unit operating
humidity
Storage temperature
Storage humidity
Altitude
Installation Requirements
Table 3-7 Installation requirements
Item
Installation mode
Height distance between
indoor and outdoor units
Maximum equivalent length of
the one-way pipe

3.3.2 Technical Specifications

Table 3-8 Technical specifications
Item
Power system
Refrigerant
Cooling capacity
Fan type
Air supply mode
Dimensions (H x W x D)
Weight
IP rating
Issue 02 (2020-12-25)
Split-Type Air Conditioner
5%–95% RH (non-condensing)
–40°C to +70°C (without refrigerant)
–40°C to +55°C (with refrigerant)
5%–95% RH (non-condensing)
0–4000 m (derated when the altitude ranges
from 1000 m to 4000 m)
Split-Type Air Conditioner
220–240 V AC, 50 Hz, 1 phase
R410A
3.5 kW
EC fan
Front air supply and rear air return
223 mm x 442 mm x 800 mm
b
Indoor unit: < 40 kg
Outdoor unit: < 50 kg
Indoor unit: IP20
Outdoor unit: IPX5
Copyright © Huawei Technologies Co., Ltd.
Split-Type Air Conditioner
Rack-mounted
–5 m to +20 m (outdoor unit placed higher)
60 m. If the length exceeds 60 m, contact the
local customer service center.
a
3 System Architecture
26