5.3.12.1 Unlocking the Cabinet Electronic Clasp Lock When a Smoke Alarm
Is Generated
Context
In this example, the smoke sensor connects to port AI/DI_1. The actual port
prevails.
Procedure
Step 1 Log in to the ECC800-Pro WebUI as an administrator.
Step 2 Choose System Settings > Linkage Control.
Step 3 Ensure that Enable linkage control function is Yes.
Step 4 On the Linkage Group tab page, set Link smoke alarm with clasp lock open to
on.
Select Link smoke alarm with clasp lock open under Linkage Group. If its value is on, the
corresponding logic configurations under Linkage Logic List are available. If its value is off, the
corresponding logic configurations under Linkage Logic List are unavailable.
Step 5 Modify the AI/DI_1 signal name.
1.
2.
3.
Step 6 Enable the AI/DI device.
1.
2.
3.
4.
----End
Follow-up Procedure
After the smoke alarm is cleared, you need to manually close the door. After the
door is closed, the door open alarm is cleared.
Issue 02 (2020-12-25)
NO TE
Choose System Settings > Signal Name Modify. The Batch Signal
Configuration tab page is displayed.
Set Device type to ECC800, set Device name to ECC800, and click OK.
On the query result tab page, set the new signal name of AI/DI_1 to Smoke
and click Submit.
Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_1
Port Settings.
Set Smoke sensor to Enable and click Submit.
Confirm that Smoke sensor type is automatically identified as Smoke sensor
or Smoke sensor(NC).
Click Unhide All Advanced Signals, and click Power Supply Parameters.
Ensure that III power supply enable(AIDI_1/DO) is Enable.