FusionModule500 Smart Mini Data Center
User Manual
Saturation
Temperatu
re (°C)
16
17
18
Oil Trap
If the outdoor unit is installed 6 m higher than the indoor unit, install an oil trap
every 6 m to 7.5 m on the gas pipe to ensure that the compressor oil flowing from
the vertical gas pipe to the oil trap can be quickly taken away when the
compressor restarts after shutdown.
Figure 4-10 Oil trap (unit: mm)
(Optional) Gas Pipe, Liquid Pipe, and Thermal Insulation Foam
Table 4-6 Specifications
Item
Gas pipe
Issue 02 (2020-12-25)
Gauge
Pressure
(MPa)
1.19
1.23
1.27
NO TE
1 MPa ≈ 10 bar ≈ 145 psi ≈ 10.2 kgf/cm
NO TICE
Copyright © Huawei Technologies Co., Ltd.
Saturation
Gauge
Temperatu
Pressure
re (°C)
(MPa)
35
2.04
36
2.1
37
2.15
2
Specifications
3/8 inch (9.52 mm), pressure withstanding
capacity ≥ 4.5 MPa
4 Installation Guide
Saturation
Gauge
Temperatu
Pressure
re (°C)
(MPa)
54
3.26
55
3.34
-
-
73