Huawei FusionModule500 User Manual page 273

Smart mini data center
Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual
Component
Alarm Name
Inverter fault
Output short
circuit
NOTE
The system
immediately
disconnects the
power output.
Intelligent
Communication
lithium
Failure
battery
monitoring
BCB Tripping
system
Single Batt.
terminal off
Issue 02 (2020-12-25)
Alarm
Possible Cause
Severit
y
Critical
The inverter output
short-circuits.
Critical
The load or cable is
short-circuited.
Critical
The network cable
communication is
interrupted.
Critical
● The battery has
● The battery circuit
● There is a security
Critical
● A battery terminal
● The battery terminal
Copyright © Huawei Technologies Co., Ltd.
discharged to the
end-of-discharge
(EOD) threshold.
breaker (BCB) box is
manually
disconnected.
risk in the battery
loop.
screw is not
tightened.
is not properly
connected to the
connector.
6 O&M
Measures
Eliminate the short
circuit at the output
port cable connection,
and then power on and
start the inverter again.
If the fault persists,
contact Huawei
technical support.
Locate and rectify the
short circuit.
Check the cable
connection to the smart
ETH gateway.
Identify the alarm
cause, rectify the fault,
and switch on the BCB
box.
● Check that battery
terminal screws are
tightened.
● Check that battery
terminals are
properly connected
to connectors.
263

Advertisement

Table of Contents
loading

This manual is also suitable for:

V100r021c00

Table of Contents