Huawei FusionModule500 User Manual page 296

Smart mini data center
Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual
Context
The water detector is installed in the cabinet and bound to the rack rail using
cable ties. The binding position is 5 U away from the cabinet bottom.
A water sensor consists of a water detection cable, water detector, and conversion
cable. The water detection cable is laid out on the floor, connecting to the water
detector placed near the collector by the conversion cable.
Figure 6-26 Water sensor components
(1) Water detector
(4) Conversion cable end B,
connected to the water
detection cable
Procedure
Step 1 Replace the water detector.
1.
2.
Issue 02 (2020-12-25)
Remove the conversion cable at the conversion port for the water detector
and conversion cable.
Remove the cover from the water detector.
Copyright © Huawei Technologies Co., Ltd.
(2) Conversion cable end A,
connected to the water detector
(5) Water detection cable end A,
connected to the conversion cable
6 O&M
(3) Conversion cable
(6) Water detection cable