FusionModule500 Smart Mini Data Center
User Manual
Item
Liquid pipe
Thermal insulation foam
Water Pipe
Drainpipes are hoses that extend 1 m out of the smart cooling product.
Condensate pipes can be PVC pipes, galvanized steel pipes, or aluminum-plastic
pipes.
Table 4-7 Specifications
Item
Automatic drainpipe
Forcible drainpipe
Pipe Support
Figure 4-11
on site conditions.
Figure 4-11 Pipe supports (unit: mm)
Issue 02 (2020-12-25)
shows supports for a refrigerant or water pipe. Select supports based
NO TE
● The height of a U-shaped pipe clamp equals the pipe diameter with thermal insulation
foam minus 5 mm. The pipe supports are to be purchased by the customer.
● The recommended material for pipe supports and clamps is 304 stainless steel.
● Install a support every 2500 mm in the straight sections of pipes, and 1000 mm away
from each bending point in the turning section.
Copyright © Huawei Technologies Co., Ltd.
Specifications
2/9 inch (6 mm), pressure withstanding
capacity ≥ 4.5 MPa
≥ 13 mm
Specifications
22 mm (outer diameter)
6 mm (outer diameter)
4 Installation Guide
74