Installing An Electrode Water Sensor - Huawei FusionModule500 User Manual

Smart mini data center
Hide thumbs Also See for FusionModule500:
Table of Contents

Advertisement

FusionModule500 Smart Mini Data Center
User Manual
Figure 4-55 Installing fasteners
When laying out the water detection cable, ensure that the water detector is close
to the cabinet to facilitate further cable connections.
Step 6 Place the water detection cable onto the fastener, secure the fastener, and keep
the water detection cable in close contact with the floor, as shown in
Figure 4-56 Securing a water detection cable
----End

4.2.6.6 Installing an Electrode Water Sensor

If the water sensor is required, perform the following steps to install it.
Procedure
Step 1 Place the water sensor on the floor under the cabinet.
Step 2 Route the water sensor cable through the cable hole in the lower cover of the
cabinet.
Step 3 Connect it to the water sensor cable connected to the ECC.
Issue 02 (2020-12-25)
NO TICE
NO TE
If multiple water detection cables are connected in series, connect the male connector of
one cable to the female connector of another.
Copyright © Huawei Technologies Co., Ltd.
4 Installation Guide
Figure
4-56.
112

Advertisement

Table of Contents
loading

This manual is also suitable for:

V100r021c00

Table of Contents