Step 2 Check the monitoring functions of smoke detector.
Table 5-6 Commissioning the detector
Check Method
Simulate a
smoky
environment
under the smoke
detector.
----End

5.3.8.2 Commissioning a T/H Sensor

Prerequisites
One end of the straight-through cable has been connected to the RS485_IN port
on the T/H sensor, and the other end has been connected to the COM port on the
ECC800-Pro.
Procedure
Step 1 Set a device address for the T/H sensor.
Operate the DIP switch on the T/H sensor to set the device address for the sensor.
Toggle switches 1 to 6 specify the device address in binary mode. ON indicates 1,
and OFF indicates 0.
Figure 5-8 DIP switch definitions for T/H sensors
Issue 02 (2020-12-25)
Normal Connection Status
Smoke DI alarm is displayed
on the active alarm page of
the app or WebUI.
NO TE
Numbers 1 and 2 indicate the DIP switch settings of T/H sensors. The DIP switch of the T/H
sensor on the front door is set to 2, and that of the T/H sensor on the rear door is set to 1.
Copyright © Huawei Technologies Co., Ltd.
5 Power-On Commissioning
Alarm Clearance Method
Disconnect the smoke
detector cable and then
reconnect it to clear the
alarm.