Mitsubishi Electric MELSEC-Q Series User Manual page 406

Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

POINT
(1) When the operation pattern is continuous positioning control or continuous
path control, the same address as the last value is specified in absolute
system or the movement amount 0 is specified in incremental system,
positioning control of movement amount 0 is executed.
(2) The BUSY signal turns ON even when position control of movement amount 0
is executed. However, since the ON time is short, the ON status may not be
detected in the PLC program.
(3) The positioning complete signal turns ON even when position control of
movement amount 0 is executed. ON time is determined by "[Pr.40]
Positioning complete signal output time".
[1] Independent positioning control (Positioning complete)
This control is set when executing only one designated data item of positioning. If
a dwell time is designated, the positioning completes after the designated time
elapses.
This data (operation pattern [00] data) becomes the end of block data when
carrying out block positioning. (The positioning stops after this data is executed.)
Positioning start signal
Start complete signal
( Md.31 Status:b14)
BUSY signal
Positioning complete signal
( Md.31 Status:b15)
Fig. 9.1 Operation during independent positioning control
V
ON
[Y10 to Y1F]
OFF
ON
OFF
ON
[X10 to X1F]
OFF
OFF
9 - 6
Chapter 9 Major Positioning Control
Positioning complete (00)
Dwell time
t
ON