[1] Parameter setting details
Setting item
Input signal logic
[Pr.22]
selection
1: Only the value specified against the axis 1 is valid for the logic selection of manual pulse generator input (b8).
2: When a servo amplifier is used and HPR is being executed, the setting is ignored. For the input logic specification
of the servo amplifier, refer to the instruction manual of the servo amplifier to be used. [CiA402 mode]
: Refer to Section 5.2 "List of parameters" for the information on detail settings.
[2] Precautions on parameter setting
To use the "External I/O signal logic switching function", set the parameters
shown in the following table.
Setting details
• Selection of logic of signals input from external
device to Simple Motion module
b0
Lower limit
b1
Upper limit
b2
Not used
b3
Stop signal
External
b4
command/
switching signal
b5
Not used
Proximity dog
b6
*2
signal
b7
Not used
Manual pulse
generator input
b8
*1
b9 to b15 Not used
(1) The external I/O signal logic switching parameters are validated when the
PLC READY signal [Y0] is turned OFF to ON. (The logic is negative right
after power-on.)
(2) If the logic of each signal is set erroneously, the operation may not be carried
out correctly.
Before setting, check the specifications of the equipment to be used.
(3) When the same external input signal is set to use to the multiple axes in
"[Pr.80] External input signal selection" or "[Pr.95] External command signal
selection ", "Input signal logic selection" of those axes should be the same.
Otherwise, the error "Input signal logic selection setting error" (error code:
938) occurs when the PLC READY signal [Y0] is turned ON, and the READY
signal [X0] will not be turned ON.
*2
0: Negative logic,
1: Positive logic
*2
Set "0".
0: Negative logic,
1: Positive logic
0: Negative logic,
1: Positive logic
Set "0".
0: Negative logic,
1: Positive logic
Set "0".
0: Negative logic,
1: Positive logic
Set "0".
14 - 13
Chapter 14 Common Functions
Factory-
set initial
Buffer memory address
value
0
31+150n
n: Axis No.-1