11.3.3 Setting the required parameters for inching operation

[Pr.1]
Unit setting
[Pr.2]
Number of pulses per rotation (AP) (Unit: PLS)
[Pr.3]
Movement amount per rotation (AL) (Unit: PLS)
[Pr.4]
Unit magnification (AM)
[Pr.11]
Backlash compensation amount (Unit: PLS)
[Pr.12]
Software stroke limit upper limit value (Unit: PLS)
[Pr.13]
Software stroke limit lower limit value (Unit: PLS)
[Pr.14]
Software stroke limit selection
[Pr.15]
Software stroke limit valid/invalid setting
[Pr.17]
Torque limit setting value (Unit: %)
[Pr.31]
JOG speed limit value (Unit: PLS/s)
: Setting always required.
: Set according to requirements (Set the initial value or a value within the setting range when not used.)
The "Positioning parameters" must be set to carry out inching operation.
The following table shows the setting items of the required parameters for carrying out
inching operation. Parameters not shown below are not required to be set for carrying
out only inching operation. (Set the initial value or a value within the setting range.)
Setting item
REMARK
Positioning parameter settings work in common for all controls using the Simple
Motion module. When carrying out other controls ("major positioning control",
"high-level positioning control", and "HPR control"), set the respective setting items
as well.
Parameters are set for each axis.
Refer to Chapter 5 "Data Used for Positioning Control" for the setting details.
Setting requirement
11 - 19
Chapter 11 Manual Control
Factory-set initial value
(setting details)
3 (PLS)
20000
20000
1 (1 times)
0
2147483647
–2147483648
0 (feed current value)
0 (valid)
300
20000