Mitsubishi Electric MELSEC-Q Series User Manual page 760

Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

Classification
Error
Error name
of errors
code
READY OFF
107
during BUSY
108
Start not possible
Common
errors
Operation cycle time
190
over error
201
Start at HP
Dog detection timing
203
fault
Count method
206
movement amount fault
Home
position
return (HPR)
207
HPR request ON
HPR restart not
209
possible
HPR zero point not
210
passed
211
ZCT read error
ABS reference point
212
read error
Error
ON
The PLC READY signal is turned from OFF
to ON when BUSY signal is turned ON.
Start is requested when start is not
possible in the axis operation state.
The calculation process time of the
positioning etc. exceeds the operation
cycle.
• When the HPR retry invalid is set, the
proximity dog method machine HPR is
started with the HPR complete flag turned
ON.
• Scale origin signal detection method
machine HPR is started with the HPR
complete flag turned ON and the
proximity dog signal turned ON.
The proximity dog signal is turned OFF
during the deceleration from an HPR speed
to a creep speed by the proximity dog
method machine HPR.
In the count method 1) and 2) machine
HPR, a parameter "Setting for the
movement amount after proximity dog ON"
is smaller than a distance necessary for
deceleration stop from an HPR speed.
The HPR request flag is turned ON when a
fast-HPR is started (positioning start No.
9002).
The restart command is turned ON after
the machine HPR is stopped using a stop
signal.
The zero point is not passed when the dog
method, count method or scale origin
signal detection method HPR is re-started,
or data set method HPR is executed.
The data is not loaded from the servo
amplifier properly upon the HPR.
• The data is not loaded from the servo
amplifier properly upon the HPR.
• The in-position signal is not turned ON
within 1.5 seconds after moving an axis to
the HP.
16 - 14
Chapter 16 Troubleshooting
Operation status at error occurrence
The READY signal [X0] is not turned ON.
The system does not start positioning.
The operation continues.
Note that the communication might not be
executed if the operation cycle is exceeded
excessively.
The machine HPR does not start.
The system stops with the setting
(deceleration stop/rapid stop) of the detailed
parameter 2 rapid stop selection (stop group
3).
(Note that the deceleration stop only occurs
during the manual pulse generator operation.)
At start
: The system does not
operate.
During operation : The system stops with the
setting (deceleration
stop/rapid stop) of the
detailed parameter 2 rapid
stop selection (stop group
3).
The fast-HPR does not start.
The restart is not carried out.
The HPR does not complete.