Issue 9.0
Frequency
Phase and Wire
Grounding
Requirements
Feeding Voltage
Output Power
AC Input I
VA@110V
VA@220V
VA@230V-240V
KWh@AC Input I x
KWh@AC Input I x
KWh@AC Input I x
BTU (KWh x 3413)
2 - 20
Table 2-16 Power Supply Specification
4 Chassis total
4 Chassis total
4 Chassis total
110V/1000
4 Chassis total
220V/1000
230-240V/1000
4 Chassis total
A dedicated outlet, separately fused and grounded for each chassis
should be installed
5.2.2

Power Supply Consumption

110VAC
47Hz - 63Hz (Rated Frequency: 50/60Hz)
Single Phase, 2 Line + PE Type
No.14 AWG Copper Wire
term
D
SLT: 25mA/ -28V
Base Chassis
Base Chassis
= 130W
4 Chassis total
= 520W
Base Chassis
Base Chassis
= 2.35A
4 Chassis total
= 9.4A
Base Chassis
Base Chassis
= 259VA
4 Chassis total
= 1036VA
Base Chassis
Base Chassis
= 0.259 KWh
= 0.262 KWh
4 Chassis total
= 1.036 KWh
= 1.048 KWh
Base Chassis
Base Chassis
= 884 BTU
4 Chassis total
= 3536 BTU
Double Pole/Neutral Fusing
(power supply fuses are located at both the L
and N side).
UNIVERGE SV8100
220VAC
230-240VAC
/OPX/DID: -48V
Base Chassis
= 130W
4 Chassis total
= 520W
Base Chassis
= 1.19A
4 Chassis total
= 4.76A
Base Chassis
= 262VA
(1.15Ax240V)
= 1048VA
4 Chassis total
Base Chassis
= 0.276 KWh
(1.15Ax240V)
4 Chassis total
= 1.104 KWh
Base Chassis
= 894 BTU
= 942 BTU
4 Chassis total
= 3577 BTU
= 3768 BTU
SV8100 System Specifications
= 130W
= 520W
= 1.15A
= 4.6A
= 276VA
= 1104VA

Advertisement