Referencing - Siemens SINAMICS S120 Function Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

In order to prevent a safety limit violation by the EPOS setpoint specification, you must
transfer the setpoint limit value (r9733) as follows to the maximum speed setpoint of EPOS
(p2594):
● r9733[0] = p2594[1]
● r9733[1] = p2594[2]
In this regard you must set the delay time for SLS/SOS/SDI (p9551/p9351), so that the
relevant safety monitoring function only becomes active after the maximum required time for
the speed to be reduced below the limit. This required braking time is determined by the
current speed, the jerk limit in p2574 and the maximum delay in p2573.
7.8.4

Referencing

After a machine has been switched on, for positioning, the absolute dimension reference
must be established to the machine zero. This procedure is referred to as referencing.
The following referencing types are possible:
● Setting the reference point (all encoder types)
● Incremental encoder
● Flying referencing (passive (p2597 = 1))
● Absolute encoder
A connector input is provided to enter reference point coordinates for all types of referencing.
This allows, e.g. changes/input via the higher-level controller. However, to permanently enter
the reference point coordinate, an adjustable parameter for this quantity is also required. As
standard, this adjustable parameter p2599 is interconnected to connector input p2598.
Drive functions
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
Active referencing (reference point approach (p2597 = 0)):
– Reference cams and encoder zero mark (p2607 = 1)
– Encoder zero mark (p0495 = 0 or p0494 = 0)
– External zero mark (p0495 ≠ 0 or p0494 ≠ 0)
– Absolute encoder adjustment
– Flying referencing (passive (p2597 = 1))
7.8 Basic positioner
*)
*)
Function modules
459

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents