Applications
11.1
Infeed switch on by a drive
Description
Figure 11-1
Using this BICO interconnection, a drive object (DO) X_INF (= all "Infeed" drive objects; i.e.
A_INF, B_INF, S_INF) can be switched on by a "VECTOR" drive object. This switch-on
version is mainly used for drive units in the "chassis" format if a single Infeed Module and a
Motor Module are used. If an application requires an automatic restart function (AR), you can
proceed as follows:
● The "automatic restart" function is activated on the "VECTOR" drive object (p1210).
● In addition to the "AR" function, the following conditions must be fulfilled:
Drive functions
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
BICO interconnection
– The "flying restart" function (p1200) must be activated on the "VECTOR" drive object
so that a flying restart can be made.
– The supply voltage must be reliably available at the Infeed Module (before the switch-
on command, an existing line contactor or motor relay must have closed).
11
815