11.1 Infeed switch on by a drive
Individual steps when restarting:
● After the line supply returns and the electronics has booted, the faults that have occurred
● The faults of the X_INF drive object are acknowledged via the BICO connection from
● The ON command (p0840) for the Infeed Module is generated via the binector output
● The switch-on attempt is interrupted if, during the restart, a fault occurs in the Infeed
● The automatic restart of the Infeed Module has absolutely no significance for the
816
at the "VECTOR" drive object as a result of its automatic restart are acknowledged
depending on the settings in p1210.
r1214.3 to p2105.
"control line contactor" of the "VECTOR" drive object (p0863.1).
Module (drive object X_INF). The fault is communicated to the "VECTOR" drive object via
the BICO connection from p1208.0 to r2139.3 shown above.
described switch-on version.
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
Drive functions