Communication
10.1 Communication according to PROFIdrive
10.1.4

Acyclic communication

10.1.4.1

General information about acyclic communication

With acyclic communication, as opposed to cyclic communication, data transfer takes place
only when an explicit request is made (e.g. in order to read and write parameters).
The "Read data record" and "Write data record" services are available for acyclic
communication.
The following options are available for reading and writing parameters:
● S7 protocol
● PROFIdrive parameter channel with the following data sets:
706
This protocol uses the STARTER commissioning tool, for example, in the online mode via
PROFIBUS.
– PROFIBUS: Data block 47 (0x002F)
The DPV1 services are available for master class 1 and class 2.
– PROFINET: Data block 47 and 0xB02F al global access, data set 0xB02E as local
access
Note
Please refer to the following documentation for a detailed description of acyclic
communication:
Reference: PROFIdrive Profile V4.1, May 2006, Order No: 3.172
Addressing:
• PROFIBUS DP, addressing is carried out via the logical address or the diagnostics
address.
• PROFINET IO, addressing is only undertaken using a diagnostics address which is
assigned to a module as of socket 1. Parameters cannot be accessed via socket 0.
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3