Note
Under the condition that the drive system was commissioned with STARTER and no
PROFIdrive telegram was activated, the infeed can be powered up by issuing an enable
signal at the EP terminals and a positive signal edge at OFF1 (p0840).
Switching off the Smart Line Module
The Smart Line Module is switched off by the same procedure used to switch it on, but in the
reverse order.
However, there is no pre-charging at switch off.
Switching off the controller with the OFF1 signal is delayed by the time entered in p3490.
This allows the attached drives to be braked in a controlled manner.
Control and status messages
Table 1- 5
Smart Infeed open-loop control
Signal name
ON/OFF1
OFF2
Enable operation
Inhibit regenerating
Acknowledge fault
Master control by PLC
Drive functions
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
Internal
Binector input
control
word
STWAE.0
p0840 BI: ON/OFF1
STWAE.1
p0844 BI: 1st OFF2 and
p0845 BI: 2nd OFF2
STWAE.3
p0852 BI: Enable operation
STWAE.6
p3533 BI: Infeed, inhibit regenerative
operation
STWAE.7
p2103 BI: 1st acknowledge faults or
p2104 BI: 2nd acknowledge faults or
p2105 BI: 3rd acknowledge faults
STWAE.10
p0854 BI: Master control by PLC
Display of internal
PROFIdrive
control word
telegram 370
r0898.0
E_STW1.0
r0898.1
E_STW1.1
r0898.3
E_STW1.3
r0898.6
E_STW1.6
r2138.7
E_STW1.7
r0898.10
E_STW1.10
Infeed
1.2 Smart Infeed
45