Siemens SINAMICS S120 Function Manual page 941

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

2. If you want to save with protection, activate the "Know-how protection without copy
3. Enter the required password in the "New password" field and enter it again in the
4. Enter the serial number of the new memory card for which the data is intended.
5. In this case, also enter the serial number of the Control Unit in the appropriate input field.
6. Click "OK" to confirm the settings you made.
Result
The data of the subproject is stored in the required encryption in your file system. With the
aid of this encrypted data, an end user can install a new memory card or Control Unit for the
drive unit.
Drive functions
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
By default, the "Without know-how protection" option is active. If you really want to store
the data without protection (not recommended), you can exit the dialog box with "OK" or
"Cancel" at this point.
protection" or "Know-how protection with copy protection" option.
Figure 12-34 Activating load to file system know-how protection
The input fields are then active. Without copy protection, only the input fields for
password input are active. With copy protection, the two input fields for the serial number
are also active. Generally, the entries in the input fields are shown in encrypted form.
"Confirm password" field.
If you have selected the "Know-how protection with copy protection" option, the input of
the Control Unit serial number is also obligatory.
Basic information about the drive system
12.14 Write and know-how protection
939