10.1.2.3
MOMRED
MOMRED (torque reduction)
This setpoint can be used to reduce the torque limit currently active on the drive.
When you use manufacturer-specific PROFIdrive telegrams with the MOMRED control word,
the signal flow is automatically interconnected up to the point where the torque limit is
scaled.
Figure 10-6
MOMRED specifies the percentage by which the torque limit is to be reduced. This value is
converted internally to the amount by which the torque is to be reduced and normalized via
p1544.
Drive functions
Function Manual, (FH1), 01/2013, 6SL3097-4AB00-0BP3
MOMRED setpoint
10.1 Communication according to PROFIdrive
Communication
645