9.10 Parallel connection of power units
Note
Exceptions for combined operation of Line Modules
Smart Line Modules may be operated together with Basic Line Modules that have Article
numbers ending with a "3" (Chassis) or a "2" (Cabinet) with one or several CUs if precisely
defined preconditions and the information in the Configuration Manual are maintained. You will
find this information in "SINAMICS - Low Voltage Engineering Manual
support.industry.siemens.com/cs/ww/en/view/83180185)".
A slight reduction of the rated current must be considered for parallel connection of power units.
The reduction of the rated current (derating) of a power unit for parallel connection is:
● 7.5 % when connecting SINAMICS S120 Basic Line Modules and SINAMICS S120 Smart
Line Modules in parallel, each of which has no current compensation control.
● 5.0% when SINAMICS S120 Active Line Modules are connected in parallel with
SINAMICS S120 Motor Modules, each of which operate with a current compensation
control.
9.10.1

Applications of parallel connections

Power units can be connected in parallel (infeeds) in the following cases:
● 6-pulse circuit
The modules connected in parallel are supplied from a two-winding transformer.
● 12-pulse circuit
The modules connected in parallel are supplied via a three-winding transformer, whose
secondary windings supply voltages with a phase shift of 30°.
Figure 9-26
518
Overview: Parallel connection of power units
(https://
Function Manual, 06/2019, 6SL3097-5AB00-0BP2