Applications
12.6 Application examples with DMC20
Encoder_3 remain active. The "Park axis" function is only enabled by setting the ZSW2.7 bit in
combination with pulse inhibit.
Note
Drives with enabled Safety functions must not be deactivated, see Section "Safety Integrated"
for further details.
Figure 12-9
Note
In order to disconnect and isolate the power unit from the DC link, additional measures must be
applied - such as DC link wiring through the DC link infeed adapter and DC link disconnecting
devices. The safety information and instructions in the Equipment Manual must be carefully
observed.
Instructions for offline commissioning with STARTER
With automatic online configuration in STARTER, the DMC20 is detected and integrated in the
topology. The following steps must be taken to commission offline:
1. Configure the offline drive device.
2. Right-click "Topology" in the project navigator and call the "Add new object > DRIVE-CLiQ
hub" context menu.
3. Configure the topology.
708
Example topology for hot-plugging for vector V/f control
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
Drive functions