7. Start the firmware update.
During the update, a check is made as to whether there is sufficient free space on the
memory card of the converter. The state of the drive objects of the Control Unit is also
checked.
Fault "F01070 project/firmware download to the memory card in progress" is output during
the upgrade. If partition 1 and partition 2 are not consistent with respect to each other, the
following alarm is output "A01073 POWER ON for backup copy to memory card required".
An entry is made in both cases in the diagnostic buffer of the Control Unit.
8. The new firmware is installed.
This process may take several minutes. The Control Unit is restarted after the firmware
update has been completed.
9. Check whether the new firmware version is installed.
The firmware version of the converter is displayed on the home page of the web server
under the converter.
13.6.6.3

Loading STARTER project data into the drive

The project files and/or firmware versions generated in the STARTER commissioning tool can
be loaded to your converter in the "Firmware update" display area of the web server. Here, you
have 2 options:
1. Merge the project files and firmware versions generated in the STARTER commissioning
tool and load to the converter.
This option is described in Step 3 of the previous Chapter "Overview (Page 764)".
2. Load individual projects, generated in the STARTER commissioning tool, into the converter.
This option is subsequently described.
Loading STARTER project data into the drive
Proceed as follows to load STARTER project files into your drive via the web server:
Requirements
You have saved the zip file with the firmware to a drive, which you can access using the
commissioning device (PG/PC, tablet or smartphone).
Drive functions
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
RDY
COM
Explanation of the LED displays
Firmware update is active.
● Do not switch off the power supply.
● Do not disconnect the motor from the converter.