8.15 OFF3 torque limits

8.15
OFF3 torque limits
Function description
If the torque limits are externally specified (e.g. tension controller), then the drive can only be
stopped with a reduced torque. If stopping in the selected time p3490 of the infeed unit has not
been completed, the infeed unit shuts down and the drive coasts down. In order to avoid this
behavior, there is a binector input (p1551), that for a LOW signal, activates the torque limits
p1520 and p1521. This means that the drive can brake with the maximum torque by
interconnecting the signal OFF 3 (r0899.5) to this binector.
Function diagrams (see SINAMICS S120/S150 List Manual)
● 5620
● 5630
● 6630
Overview of important parameters (see SINAMICS S120/S150 List Manual)
● p1520[0...n]
● p1521[0...n]
354
Servo control - Motoring/generating torque limit
Servo control - Upper/lower torque limit
Vector control - Upper/lower torque limit
Torque limit upper/motoring
CO: Torque limit lower/regenerative
Function Manual, 06/2019, 6SL3097-5AB00-0BP2