3. For an induction or reluctance motor, immediately after the speed has been determined,
magnetization starts (p0346).
4. The current speed setpoint in the ramp-function generator is then set to the current actual
speed value.
The ramp-up to the final speed setpoint starts with this value.
Example
After a power failure, a fan drive can be quickly reconnected to the running fan motor by means
of the "flying restart" function.
Figure 6-23
Figure 6-24
Drive functions
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
Application example: Induction motor without encoder
ON
Application example: Induction motor with encoder
Vector control
6.17 Flying restart
t
t
267