Procedure
To configure the response for extended shutdown, proceed as follows:
1. Configure the stopping response with the parameter setting p0888 = 1 (N-set) or p0888 =
4 (N-actual).
2. Set the time in parameter p0892 for which the last setpoint from r1438 and the last actual
value from r0063 are frozen before braking is initiated.
3. Select the OFF ramp with parameter p0891.
Figure 9-29
9.11.4.2

Extended retract

Overview
In the case of a fault, the objective is to approach a retraction position. The retraction method
is used as long as the drive is still capable of functioning. The function is parameterized and
operates on an axis-specific basis. Interpolating coupling of the axes is not realized.
Procedure
To configure the response for extended retraction, proceed as follows:
1. Configure the retract response with p0888 = 2.
2. Define the retraction speed with parameter p0893.
Drive functions
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
p0888 = 1 "extended stopping (drive-based)"
n
r1438
r0063
Function initiation
p0888 = 4 "extended stopping (drive-based)"
OFF ramp with timer
Selection
Timer
Off ramp
p0892
p0891 (OFF3)
Drive follows
frozen
setpoint
Drive follows
the last
actual value
OFF3
Function modules
9.11 Extended stop and retract
OFF1
t
535