Vector control
6.2 Vector control without encoder (SLVC)
As a consequence, the "Passive load" function is automatically activated.
Note
If p0500 is parameterized when commissioning the motor, the calculation is carried out
automatically via p0340 and p3900. p0578is is then set automatically.
Closed-loop control without changeover between closed-loop and open-loop speed control is
restricted to applications with passive load:
A passive load only has a reactive effect on the drive torque of the driving motor at the starting
point, e.g. high inertia masses, pumps, fans, centrifuges, extruders, travel drives, or horizontal
conveyors.
Standstill without a holding current is possible for as long as required. Then, at standstill, only
the magnetizing current is impressed in the motor.
Note
Generator operation
Steady-state generator operation at frequencies close to 0 Hz is not permissible in this
operating mode.
Figure 6-3
Vector control without an encoder
Blocking drives
If the load torque is higher than the torque limiting of the encoderless closed-loop vector control,
the drive is braked to zero speed (standstill). In order that the open-loop controlled mode is not
selected after the time p1758, p1750.6 can be set to 1. Under certain circumstances the "Motor
blocked delay time" (p2177) must be increased.
Note
Exception for reversing drives
It is not permissible to use this setting if the load can force the drive to reverse.
212
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
Drive functions