8.13

DC braking

Overview
You set the "DC braking" function in the parameters p1231[0...n]. You can determine the
current status of the function in r1239.
Supported Motor Modules
The function has been released for Motor Modules in the Booksize and Chassis formats.
Requirement
● Operation with induction motors
Function description
Motor accelerates uncontrollably for pulling loads
For pulling loads, when DC braking is used, during the demagnetization time, the motor can
accelerate uncontrollably. This can result in severe injury or death. An additional supporting
mechanical brake is only closed after the demagnetization time - when the motor is already
rotating - and therefore does not prevent the motor from accelerating uncontrollably.
● Do not use DC braking for pulling loads.
Using the "DC braking" function, you can brake induction motors down to standstill. With this
function, after a demagnetization time, a direct current is injected in the stator windings of the
induction motor. The motor is braked by the direct current.
The function is preferably used in the following cases:
● It is not possible to ramp down the drive in a controlled fashion
● Operation with a line module that is not capable of energy recovery
● Operation without a braking resistor
8.13.1

Configuring the function via parameters

Procedure
Carry out the following steps to configure the function via parameters:
Drive functions
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
WARNING
Basic functions
8.13 DC braking
339