Permanent-Magnet Synchronous Motors - Siemens SINAMICS S120 Function Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Active loads
Active loads that can be used to reverse the drive, e.g., hoisting gear, must be started in the
open-loop speed control mode. In this case, bit p1750.6 must be set to 0 (open-loop controlled
operation when the motor is blocked). The static (steady state) torque setpoint p1610 must be
greater than the maximum occurring load torque.
Note
Loads that can drive the motor
For applications with high regenerative load torques at low speeds, p1750.7 can also be set to
1. As a result, the speed changeover limits of the motor model are increased and a faster
changeover can be made into open-loop controlled operation.
6.2.2

Permanent-magnet synchronous motors

Description
Permanent-magnet synchronous motors (PMSM) are always started and reversed in the open-
loop controlled mode. The changeover speeds are set to 10% as well as 5% of the rated motor
speed. Changeover is not subject to any time condition (p1758 is not evaluated). Prevailing
load torques (motor or regenerative) are adapted in open-loop operation, facilitating constant-
torque crossover to closed-loop operation even under high static loads. Whenever the pulses
are enabled, the rotor position is identified.
Figure 6-4
Closed-loop controlled operation down to f = 0 Hz
The actual rotor position can be continuously determined down to 0 Hz (standstill). With
Siemens 1FW4 and 1PH8 torque motors, the load can be maintained at standstill or, from
standstill, the motor can accelerate any load up to rated torque.
Drive functions
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
Zero point and starting in the open-loop controlled mode at low speeds
6.2 Vector control without encoder (SLVC)
Vector control
213

Advertisement

Table of Contents
loading

Table of Contents